Many buyers pick a cabinet by rack units alone, then find the recorder or server will not fit because of depth, or that the cables have nowhere to go. Avayo offers several depths and widths for most heights. This guide explains how to choose the right depth and width.
1. Available depths
- 4U wall: 350 or 450 mm.
- 6U wall: 350, 450, 550 or 600 mm.
- 9U wall: 450, 550, 600 or 800 mm.
- 12U and 15U wall: 550, 600 or 800 mm.
- 18U wall: 600 mm.
- Floor 18U to 42U: 600, 800 or 1,000 mm at 600 mm wide, some heights at 800 mm wide and 1,000 mm deep, plus a 42U model at 800×800 mm.
2. How to work out the depth you need
Start with the deepest device you will install and take its depth from the datasheet, then add room behind it for power plugs and network cables, because a tightly bent cable degrades over time. Remember that the listed cabinet depth is external, and that the mounting profiles in Avayo cabinets are adjustable front and rear, so you can move them forward or back to suit the devices.
3. Suggested depths by equipment
| Equipment | Suggested depth | Example |
|---|---|---|
| Patch panels and short switches | 350 to 450 mm | Avayo AVE-W04S-6045B |
| Switches and a recorder | 550 to 600 mm | Avayo AVE-W12S-6060B |
| Deeper devices | 800 mm | Avayo AVE-W09S-6080B |
| Rack servers | 1,000 mm in a floor cabinet | Avayo AVE-F4261-20B |
These are general suggestions; what counts is the actual depth of your devices in their datasheets.
4. Width: 600 or 800 mm?
All wall cabinets and most floor cabinets are 600 mm wide, which suits most networks. An 800 mm width leaves space on both sides of the 19-inch profiles to run cable bundles vertically and fit vertical cable managers, which matters in distribution cabinets that receive hundreds of cables. Avayo offers 800 mm-wide 22U, 27U, 32U, 37U and 42U models at 1,000 mm deep, and a 42U model at 800×800 mm.
5. Room space
Measure the room before ordering: an 800×1000 mm floor cabinet needs more floor area, plus clearance in front and behind for opening doors and maintenance. Check the room door and corridors too, since a 42U cabinet is 2,000 mm tall.
Choose the depth for the deepest device you expect to add later, not only for the devices you have today; replacing a cabinet after commissioning is costly.
For tall server room cabinets, see our guide to Avayo 32U, 37U and 42U cabinets.
Products mentioned in this guide
- Avayo AVE-W04S-6035B – 4U wall, 350 mm deep
- Avayo AVE-W04S-6045B – 4U wall, 450 mm deep
- Avayo AVE-W12S-6060B – 12U wall, 600 mm deep
- Avayo AVE-W09S-6080B – 9U wall, 800 mm deep
- Avayo AVE-F4266-20B – 42U floor, 600×600 mm
- Avayo AVE-F4268-20B – 42U floor, 600×800 mm
- Avayo AVE-F4261-20B – 42U floor, 600×1000 mm
- Avayo AVE-F2281-12B – 22U floor, 800 mm wide
- Avayo AVE-F4288-20XB-GS – 42U floor, 800×800 mm
- Avayo AVE-F4281-20B-GP – 42U floor, 800×1000 mm, glass door
Frequently asked questions
Can I put a server in a wall cabinet?
Rack servers are usually deep and heavy, and wall cabinets carry up to 30 kg, so a 1,000 mm-deep floor cabinet is the better choice.
What are adjustable profiles for?
They let you move the mounting profiles forward or back to fit the device depth and leave room for cables.
Does an 800 mm-wide cabinet take 19-inch devices?
Yes, every model has a 19-inch mounting opening; the extra width is for cables.
Need help choosing the right Avayo solution?
Rasid's team in Riyadh helps you choose the right equipment for your site and handles supply, installation and programming for businesses, hotels and homes in Saudi Arabia. Message us on WhatsApp +966559790746 or request a solution for your project.